RITTAL SK 3314.130 Liquid Cooling Package LCP Rack CW/CWG

RITTAL SK 3314.130 Liquid Cooling Package LCP Rack CW/CWG

分类: Liquid Cooling Package 当前有货
欲了解更多详情,请游览我们的官方网站 improtechonline.com

详情

Product description

Article number:
SK 3314.130
Design
Rack cooling
CW
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Control of the server inlet temperature
With redundant temperature sensor integrated at the air end as standard
Optimum adaptability due to dynamic, continuous control of the cold water volume flow
By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
Modular fan units for a demand-based cooling output (fan replacement without tools, also possible during operation)
Fan modules configurable as n+1 redundancy
Standard 3-phase connection for electrical redundancy
The separation of cooling and enclosure prevents the ingress of water into the server enclosure
A footprint of max. 0.36 m² for all cooling services
Improved heat recovery, thanks to high water return temperatures when using LCP CW glycol variants, for example in combination with a heat pump
Optimum access for maintenance and servicing from the front and rear
Function principle
The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
Material
Enclosure: Sheet steel
Front door: Aluminium, anodised/spray-finished
Colour
Enclosure: RAL 7035
Front door: Vertical sections, silver coloured and horizontal sections, RAL 9005
Options
Fully integrated fire detection and extinguisher system
Automatic server enclosure door opening
Direct connection of an additional 16 CMC III sensors possible
Racks 2200 mm high
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
Direct connection of the unit via SNMP over Ethernet (2 Ethernet ports for simpler cascading of up to 16 LCPs)
Integration into RiZone OTM Suite (extended measuring and management functions, values can be transferred and visualised)
Note on Model No.
Optimised condensate management also at low water inlet temperatures, available upon request.
Total cooling output/Number of fan modules
10 kW/1
20 kW/2
30 kW/3
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
Number of fan modules in supplied state
1
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,000 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
200 V - 240 V, 1~, 50 Hz/60 Hz
346 V – 415 V, 3~, 50 Hz/60 Hz
Max. cooling output
30 kW
Type of electrical connection
Connector
Duty cycle
100 %
Cooling medium
Water
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Two-way control valve
Water connections
DN 40 (G 1½'' external thread)