Optimum adaptability due to dynamic, continuous control of the cold water volume flow
Fan modules may be replaced while the system is operational
Function principle
The LCU CW is built into the network/server rack adjacent to the 482.6 mm (19'') mounting level. The heated air is drawn in at the rear third of the rack, cooled via the heat exchanger, and then expelled again from the front section of the rack.
Material
Sheet steel, spray-finished
Colour
RAL 9005
Supply includes
1 liquid cooling unit CW
1 support for LCU CW
3 m braided hose (for condensate discharge)
2 angular hose connectors 90°
12 screws M5 x 12 self-tapping NZ/TX30
1 female multi-point connector (7-pole)
1 set of assembly, installation and operating instructions
Options
Connect a maximum of 16 CMC III sensors
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Temperature control
Control of the server inlet temperature
IP protection category to IEC 60 529
IP 20
Duty cycle
100 %
Refrigerant/cooling medium
Cooling medium: Water
To fit
Enclosure type: VX IT Standard 19'' mounting angles
Width: ≥ 800 mm
Height: ≥ 2,000 mm
Depth: ≥ 1,000 mm