RITTAL SK 3314.530 Liquid Cooling Package LCP Inline CW/CWG

RITTAL SK 3314.530 Liquid Cooling Package LCP Inline CW/CWG

Kategori: Liquid Cooling Package Tersedia
Untuk maklumat lanjut, lawati laman web rasmi kami di improtechonline.com

Penerangan

Product description

Article number:
SK 3314.530
Design
Suite cooling
CW
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Optimum adaptability due to dynamic, continuous control of the cold water volume flow
By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
Modular fan units for a demand-based cooling output (fan replacement without tools, also possible during operation)
Fan modules configurable as n+1 redundancy
Standard 3-phase connection for electrical redundancy
With redundant temperature sensor integrated at the air end as standard
The separation of cooling and enclosure prevents the ingress of water into the server enclosure
A footprint of max. 0.36 m² for all cooling services
Improved heat recovery, thanks to high water return temperatures when using LCP CW glycol variants, for example in combination with a heat pump
Optimum access for maintenance and servicing from the front and rear
Function principle
The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
Material
Enclosure: Sheet steel
Front door: Aluminium, anodised/spray-finished
Colour
Enclosure: RAL 7035
Front door: Vertical sections, silver coloured and horizontal sections, RAL 9005
Options
Direct connection of an additional 16 CMC III sensors possible
Racks in height 2200 mm, additional baffle plate separator including humidity sensor
Monitoring
Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
Direct connection of the unit via SNMP over Ethernet (2 Ethernet ports for simpler cascading of up to 16 LCPs)
Integration into RiZone OTM Suite (extended measuring and management functions, values can be transferred and visualised)
Note on Model No.
Optimised condensate management also at low water inlet temperatures, available upon request.
Total cooling output/Number of fan modules
10 kW/1
20 kW/2
30 kW/3
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
Number of fan modules in supplied state
1
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Set forward
Rated operating voltage
200 V - 240 V, 1~, 50 Hz/60 Hz
346 V – 415 V, 3~, 50 Hz/60 Hz
Max. cooling output
30 kW
Type of electrical connection
Connector
Duty cycle
100 %
Cooling medium
Water
EC fan
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Two-way control valve
Water connections
DN 40 (G 1½'' external thread)